FL-XT FLame eXTinguish

Quick Fire Suppression

2022 Fire Causes in Korea

Number of Fires by Cause of Ignition

Electrical
factors:
10,011 cases
Others
2,909
Unknown
3,670
Mechanical
factors
3,856
Negligence
19,667
Number of Fires by Cause of Ignition graph

Number of Electrical Equipment Fires

Switch/
panel boards
494cases
Batteries/
capacitors:
161
Integrating
wattmeters
110
Solar power
generation
99
Low voltage
circuit breakers
71
Others
421
Number of Electrical Equipment Fires graph

[Source : Korea National Fire Data Center]

Product Information

FL-XT Series(Compact Space Fire Extinguishing Equipment)

Compact fire suppression device that automatically detects and
extinguishes fires in small, confined spaces

Extinguishing agent discharge port

Fully sealed container design

Lightweight and small-scale, designed for use with cabinet-type panel boards, etc.

Automatic detection of heat flow

Halogenated Extinguishing Agent

소공간 소화용구

Installation Target

  • MCC control panels of always-on power devices for ventilation, exhaust, or drainage in underground facilities
  • Inverters and connection panels for solar power installations that pose a higher fire risk due to limited accessibility by maintenance personnel
  • Panel/switch boards, electrical and control panels, server rooms, computing racks, and conveyors used on manufacturing lines, etc.
  • Panel/switch boards, condensing units, etc. in heat-generated, fire-prone areas such as traditional markets

Switch boards and panel boards at risk of overheating and subsequent fire incidents Ideal for preventing the spread of fires in spaces that are either fully enclosed or semi-enclosed

Features

Established track record with certified performance
for 4 years since product launch

Spec.Small

Installation Method : Flexible top mounting

KTL Certification : PB12021-016

Classification FL-XT 40 FL-XT 120 FL-XT 360
Protective Coverage Up to 0.04m³ (40L) Up to 0.12m³ (120L) Less than 0.36m³ (360L)
Content Weight (g) 56g 76g 215g
Container Thickness (mm)/
Thread Size (inch)
1.2mm / ½-20” 2.0mm / 5 / 8-18” 2.0mm / 5 / 8-18”
HFC-125 Agent (g) 56g 76g 215g
Activation Temp. (℃) 68℃ 68℃ 68℃
Charging Gas & Pressure N₂ : 7.0Mpa N₂ : 7.0Mpa N₂ : 7.0Mpa
Ambient Temp. for Operation (℃) -20 ~ +50 -20 ~ +50 -20 ~ +50
Diameter (D), Length (L) 30mm, 200mm 30mm, 240mm 40mm, 320mm

Spec.Medium

Installation Method : Vertically on the top side

KTL Certification : PB12021-016

Classification FL-XT 1200 FL-XT 3000
Protective Coverage Up to 1.2m³ (1,200L) Up to 2.9m³ (3,000L)
Container Weight /
Content Weight (g)
2,625g / 980g 6,370g / 3,400g
HFC-125 Agent (g) 980g 1,900g
Activation Temp. (℃) 68℃ 68℃
Charging Gas & Pressure N₂ : 4.2Mpa N₂ : 2.5Mpa
Ambient Temp. for Operation (℃) -20 ~ +40 -20 ~ +40
Diameter (D), Length (L) 91mm, 395mm 114mm, 560mm

Examples of Protective Coverage

Small Cm Medium Cm
FL-XT 40 FL-XT 120 FL-XT 360 FL-XT 1200 FL-XT 3000
Protective Coverage
0.04m³ = 40ℓ
Protective Coverage
0.12m³ = 120ℓ
Protective Coverage
0.36m³ = 360ℓ
Protective Coverage
1.215m³
Protective Coverage
2.880m³

Photos of Installation Process

Before During After

Installation Cases

Air Conditioner's Condensing Units




Fire Suppression at Dangjin Cultural Center

Fire Suppression at Dangjin Cultural Center

Certification and Patent Status

K-Mark Certification KFI Mark Certificate
(FL-XT 40)
KFI Mark Certificate
(FL-XT 60)
KFI Mark Certificate
(FL-XT 120)
Patent for Invention Certificate Design Registration Certificate
U.S. Patent Certificate

Authorized Dealer Information

For Product Inquiries